Novel Modified Characteristic Curve of Distance Relays by Consideration of Harsh Weathers

Navid Bayati*

*Corresponding author for this work

Research output: Chapter in Book/Report/Conference proceedingArticle in proceedingsResearchpeer-review

Abstract

One of the main challenges in the operation of power systems is the protection of transmission lines against faults. In the majority of power systems, distance relays locate the faults in transmission lines with high speed, reliability, and selectivity. Moreover, due to the installation of distance relays in each line, the whole of a transmission system is also covered by these devices. The operation of these devices depends on the parameters of transmission lines, and the design of their settings is based on the assumption of fixed transmission line parameters. However, due to the harsh weather in Nordic countries, this assumption is not true, and variation in weather conditions rapidly will have an impact on the accuracy of these devices significantly. In this paper, the impact of harsh weather on the operation of distance relays is investigated, and an improved distance relay setting is proposed to improve their operation of them. The effectiveness of the proposed method is proved during different conditions by simulations.

Original languageEnglish
Title of host publication2022 IEEE International Conference on Environment and Electrical Engineering and 2022 IEEE Industrial and Commercial Power Systems Europe, EEEIC / I and CPS Europe 2022
Number of pages4
PublisherIEEE
Publication date2022
ISBN (Electronic)9781665485371
DOIs
Publication statusPublished - 2022
Event2022 IEEE International Conference on Environment and Electrical Engineering and 2022 IEEE Industrial and Commercial Power Systems Europe, EEEIC / I and CPS Europe 2022 - Prague, Czech Republic
Duration: 28. Jun 20221. Jul 2022

Conference

Conference2022 IEEE International Conference on Environment and Electrical Engineering and 2022 IEEE Industrial and Commercial Power Systems Europe, EEEIC / I and CPS Europe 2022
Country/TerritoryCzech Republic
CityPrague
Period28/06/202201/07/2022

Keywords

  • fault
  • harsh weather
  • Protection
  • relay